Chiller Enclosures

Noise Barriers’ Chiller Enclosures provide turnkey noise reduction for rooftop and ground-level HVAC chillers. Built from QuietLine barrier wall technology, these enclosures combine acoustic absorption, ventilation, and weatherproofing in a modular system.

Product Information

Support Documents

V-Stack®

The V-Stack is Noise Barriers most versatile panel system. This panel has a solid skin on one side and a sound absorptive skin on the other side. The panel is 4” or 5” thick depending on span and wind-loading, 16 gauge solid skin with a 22 gauge perforated skin. Perforated skin has 3/32” diameter holes on 3/16” staggered centers. Weight: 5.2 lbs./sq.ft. All galvanized construction using “paint ready” galvanneal A-60 steel with internal stiffeners 24” on center. The face sheets are spot welded to the panel framing channel. All stiffeners and panel channel framing is minimum 18 gauge steel. THE PANELS CAN BE INSTALLED VERTICALLY OR STACK HORIZONTALLY ONE ON TOP OF ANOTHER BETWEEN COLUMNS. Panels lift out of the crate without handling and install without fasteners. Maximum panel size 60” x 190”. The acoustic fill is non-combustible, sound absorbing fiberglass or mineral wool. Prime painting or factory finish painting is available.

Model H/P

This panel has a solid skin on one side and a sound absorptive skin on the other side. 4” thick, 16 gauge solid skin with a 22 gauge perforated skin. Perforated skin has 3/32” diameter holes on 3/16” staggered centers. Weight: 5.2 lbs./sq.ft. All galvanized construction using “paint ready” galvanneal A-60 steel with internal stiffeners 24” on center. The face sheets are spot welded to the panel framing channel. All stiffeners and panel channel framing is minimum 18 gauge steel. THE PANELS CAN BE INSTALLED VERTICALLY OR STACK HORIZONTALLY ONE ON TOP OF ANOTHER BETWEEN COLUMNS. PANEL IS CONNECTED TO PANEL WITH AN “H” JOINER. Maximum length is 168”. The acoustic fill is non-combustible, sound absorbing fiberglass or mineral wool. Prime painting or factory finish painting is available.

Model H/H

This panel is reflective both sides (non-absorptive). 4” thick, 16 gauge solid skin with a 16 gauge solid skin. Weight: 6.7 lbs./sq.ft. All galvanized construction using “paint ready” galvanneal A-60 steel with internal stiffeners 24” on center. The face sheets are spot welded to the panel framing channel. All stiffeners and panel channel framing is minimum 18 gauge steel. THE PANELS CAN BE INSTALLED VERTICALLY OR STACK HORIZONTALLY ONE ON TOP OF ANOTHER BETWEEN COLUMNS. PANEL IS CONNECTED TO PANEL WITH AN “H” JOINER. Maximum length is 168”. The acoustic fill is non-combustible, sound absorbing fiberglass or mineral wool. Prime painting or factory finish painting is available.

Brown storage container with metallic lids for organized waste management.

QuietMod Chiller Enclosure - Carmel, IN

Noise Barriers provided a turnkey solution ― design, supply and installation of this chiller enclosure and achieved the goal of the city. There have been no more noise complaints.

Read Case Study



industrial acoustic applications

INDUSTRIAL APPLICATIONS

See how Noise Barriers’ Chiller Enclosures and other products work in an Industrial Environment

View Render

Features

  • Custom sizes for any chiller or rooftop application
  • NRC 0.95+ and STC 37+ performance ratings
  • Integrated silenced ventilation options
  • Weather- and corrosion-resistant materials
  • Quick-install modular design for minimal downtime

Applications

  • Hospitals and healthcare facilities
  • Universities and schools
  • Corporate campuses and commercial buildings
  • Industrial plants with large HVAC chillers

Acoustic Performance

Sound Transmission Loss Data, dB

Octave Band Center Frequency, Hz 125 250 500 1K 2K 4K STC
Barrier Panels
V-Stack Aluminum 14 20 31 42 40 52 33
V-Stack Steel 22 26 35 45 47 48 38
Type SL 18 26 35 45 49 52 37
Type SL-R 18 26 35 45 49 52 37
Type SL-R Concealer 18 26 35 45 49 52 37
H/P 42 V-Stack 23 31 40 49 56 62 42
H/P 38 24 25 33 43 50 55 38
H/P 42 23 31 40 49 56 62 42
H/P 44 27 34 41 46 53 59 44
H/H 50 26 44 50 54 57 64 50
H/H 52 37 43 47 53 54 57 52
All tests performed by an independent NVLAP accredited acoustical testing facility. The test method conforms with ASTM Designations E90-99 or E90-02 and E413-87.

Octave Band Center Frequency, Hz 125 250 500 1K 2K 4K NRC
Sound Absorption Coefficients Barrier Panels
V-Stack Aluminum 0.89 1.23 1.18 1.08 1.06 0.95 0.95 (1.15)
V-Stack Steel 0.86 1.20 1.17 1.07 1.08 1.02 0.95 (1.15)
Type SL (All Models) 0.92 1.15 1.22 1.13 1.08 1.04 0.95 (1.15)
H/P 42 0.68 1.06 1.12 1.08 1.03 0.98 0.95 (1.05)
All tests performed by an independent NVLAP accredited acoustical testing facility. The test method conforms with the requirements of the ASTM Standard Test Method for Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method: ASTM C423-90a and E795-00.

See The Chiller Enclosures Gallery